Product Documentation
Official Autotrol documentation is provided to support installation, configuration, and maintenance of the Magnum control valve with 764 Logix metered control.
- Autotrol Magnum Control Valve Data Sheet
- Autotrol 764 Logix Metered Control Data Sheet
- Autotrol 293/764 Magnum Control Valve Manual
FEATURES AND BENEFITS
The Autotrol Magnum valve combined with the Logix metered control platform is engineered for high-capacity filtration applications requiring precision, durability, and flexible system control.
- The Logix series provides advanced control functionality for the Magnum valve.
- Cartridge-style assembly allows easy installation and cleaning of injectors, refill components, and brine screen features.
- Magnum CV valve features 1-1/2″ inlet and outlet connections.
- Magnum IT valve features 2″ inlet and outlet connections.
- Time-tested Duraflow flapper provides frictionless sealing for extended service life.
- Fiber-reinforced polymer valve body offers superior strength while remaining non-corrosive and UV resistant.
- Optical sensor ensures precise cycle positioning.
- Fully adjustable 3- or 5-cycle control supports efficient and reliable system operation.
- Continuous service flow rate of 76 GPM with a backwash rate of 89 GPM.
- Backwash capability accommodates softener and filter tanks up to 36 inches in diameter.
- Designed for use in single or multiple tank system configurations.
- Super capacitor maintains time of day during power outages.
- Programming is stored in memory and retained during power interruptions.
- History data tracking supports valve performance monitoring.
SPECIFICATION
Technical specifications outlining operating limits, connection sizes, and configuration details of the Autotrol Magnum IT filter valve with 764 Logix metered control.
- Part Number: 4001324 (Autotrol 293 Magnum IT Filter Valve, 4-Cycle, 293/764L-NHWB)
- Model Number: 293/764L Logix Metered Filter Valve, Multi Tank – Remote Lockout
- Tank Thread: 4″
- Inlet / Outlet Threads: 2″ NPT or BSPT, female, CPVC
- Brine Line Connection: 3/4″ NPT
- Drain Line Connection: 1-1/2″ NPT or BSPT, female, CPVC
- Riser Tube Diameter: 1-1/2″
- Working Pressure: 25–100 psi (1.72–6.9 bar)
- Water Temperature: 35–100°F (2–38°C)
- Bypass: No hard water bypass cartridge
- Notes: 1.5″–2″ NPT/CPVC fittings and drain line flow controller sold separately
Pentair 3 Year Limited Warranty on Autotrol Magnum
Reviews